How to specify industrial duct bellows dimensions

A bellows order can fail even when the duct size looks correct: “100 mm duct” does not say whether the connection is internal, external, flange-mounted, or measured between faces. By the end, you will be able to prepare a dimensioned specification covering the opening, movement, mounting interface, operating envelope, inspection conditions, and supplier tolerances.

Key takeaways

  • Separate bellows, duct opening and installation-envelope dimensions.
  • Measure the opening and gap with the duct in its installed state.
  • Calculate relaxed length from movement, compression and extension limits.
  • State flange details, clearances, tolerances and inspection conditions on the drawing.

Which dimensions belong on an industrial duct bellows drawing?

Industrial duct bellows dimensions must define the bellows, the duct opening, and the installation envelope separately. Record each dimension with its measurement condition and state whether end collars, cuffs, clamping frames, or flanges are included.

DimensionRequired definition
Relaxed bellows lengthFree, unloaded length
Compressed bellows lengthShortest specified axial length
Installed or nominal lengthLength at the operating position
Maximum extended lengthLongest permitted axial length
Axial strokeDifference between compressed and extended lengths
Nominal width and heightRectangular connection size, not usable flow area
Circular diameterState nominal diameter or clear inside diameter
Convoluted heightRadial or transverse fold projection
Convolution count or convolution pitchLink to a dimensioned end-treatment drawing; end folds often differ from active folds
Corner radiusState inside, outside, or centreline radius
Maximum clearance envelopeFull space occupied during movement, including fittings and folds
Bend radiusIdentify inside, outside, or centreline radius, and whether it applies to static installation or repeated motion

For the duct, specify clear internal opening, outside envelope, nominal connection size, wall thickness, liner thickness, folded sidewalls, and flange-to-flange installation length. Width × height alone does not establish usable flow area because wall thickness, corner radius, liners, and folded sidewalls reduce the passage.

State whether every value is measured free-standing or installed, at what temperature, under what applied tension or compression, and from which fixed reference datums. Without those conditions, the relaxed bellows length and compressed bellows length can produce different results. Convolution pitch must not be calculated from total length alone.

How do you measure the duct opening and installation gap on site?

Measure from one identified datum, not from whichever edge is easiest to reach. Record the connection type first, because “fits a 100 mm duct” does not define the mounting method or the industrial duct bellows dimensions.

Connection typeMeasurement referenceRecord
Inside-mountedActual internal sealing planeClear duct opening, insertion depth and gasket seating width
Outside-mountedDuct outside wall or collar datumOutside width, height, wall thickness and clamp space
Flange-mountedMating flange faceFlange-to-flange length, hole pattern, fastener access and sealing face

1. Measure the clear duct opening at the actual sealing plane. Then record outside width and height, wall thickness, corner radius, and any liner or folded edge that reduces passage area.

2. For a round duct, record both nominal diameter and measured round duct inside diameter. Do not replace the measured value with the nominal size.

3. Measure the gap between fixed mounting datums at several points, including the flange-to-flange length. Record the smallest and largest readings caused by squareness or misalignment.

4. Mark insertion depth, gasket seating width, clamp space, fastener access, and nearby cable or hose obstructions. State the datum from which every flange, hole, and length is measured.

5. Photograph and dimension elbows, split ducts, offset transitions, unequal end frames, and non-rectangular sections. Require a dimensioned drawing for these shapes instead of a single size label.

How should movement and the required relaxed length be calculated?

For industrial duct bellows dimensions, define movement as a vector set, not as one stroke number. State axial compression, axial extension, lateral offset in each relevant direction, angular movement or flange rotation, and torsional movement relative to named mounting datums.

A bellows sized for axial travel can buckle, bind, or lose clear area when that travel occurs laterally.

1. Record the measured duct gap and chosen installed length. Identify end clearances at both mounts, then calculate compressed and extended positions from the full compression and extension range.

2. Set the required relaxed length so it accommodates those positions, the end clearances, and the manufacturer’s minimum convolution spacing. Do not derive fold count from total length alone; check active convolution count, pitch, end-fold geometry, and allowable compressed height.

3. Add the motion sequence, cycle count or design life, stroke frequency, speed, and acceleration. A bellows that reaches its required length once can fail when the same movement repeats millions of times.

4. State the pressure differential and vacuum level. Negative pressure can collapse the section and reduce its clear opening, so specify reinforcement, anti-collapse support, or allowable deformation.

Tie temperature limits to dimensional performance. Account for thermal expansion, sag, stiffening, softening, and changes in attainable stroke at the operating temperature, rather than listing temperature only as a material limit. Verify that the relaxed, installed, compressed, and extended lengths remain usable throughout that range.

What flange and clearance details determine whether the bellows will fit?

Industrial duct bellows dimensions become inspectable at the connection when the drawing defines the flange face, datum, and orientation. State whether each dimension describes the clear internal opening, outside envelope, or nominal connection size; “fits a 100 mm duct” does not show whether the bellows mounts over, inside, or against it.

  • Flange width and flange thickness
  • Gasket seating area and seal installation clearance
  • Insertion depth and the mating-face datum
  • Bolt-hole diameter, hole count, and bolt-hole pattern, including pitch-circle diameter or centre-to-centre spacing
  • Edge margins, corner treatment, and the orientation clocking from a named datum
  • Hole type: through-hole, slot, or threaded hole
  • Clearance around bolts, washers, clamps, tools, and fastener removal
  • Rectangular corner radius, because it changes flow area, fold geometry, minimum bend radius, and corner interference during collapse

For unequal inlet and outlet sizes, offset transitions, elbows, split ducts, or different end frames, attach one dimensioned interface drawing showing both ends, their relative position, and every angular offset. Add the maximum envelope for lateral sweep, fold bulging, flange rotation, sag, nearby equipment, and installation access.

Identify material thickness, seam or weld locations, internal liners, reinforcement, convolution pitch, and end-treatment details when they alter the folded envelope or minimum radius. A nominal length and opening alone cannot predict fit.

How should you document tolerances, inspection states, and supplier acceptance?

Document industrial duct bellows dimensions as an acceptance specification, not only as nominal width, height, or diameter. Put dimensional tolerances on every functional feature: clear opening, installed length, compressed and extended lengths, axial stroke, flange location, hole pattern, corner radius, minimum bend radius, and allowable deformation under pressure or vacuum.

1. Define inspection states as fully compressed, nominally installed, and fully extended, where those states apply. Inspecting only the free unloaded part can hide clear-area loss, flange squareness errors, hole misalignment, fold interference, or failure to achieve the required stroke.

2. Use ISO 2768-1 only for general linear and angular tolerances that suit the part. Do not use it as a substitute for purpose-built dimensional tolerances on flexible fabric or elastomer bellows, especially where movement changes the measured shape.

3. State the measurement condition beside each critical dimension: temperature, mounting condition, applied tension or compression, and whether the bellows is measured free-standing or installed. Require the supplier to define what “overall length” includes, including collars or mounting frames.

4. Ask for the quoted maximum operating envelope, pressure differential or vacuum level, support or reinforcement against collapse, and allowable deformation at those conditions. Include bellows inspection results for clear area, squareness, hole alignment, fold clearance, and achieved stroke.

When comparing SCUTES INDIA PRIVATE LIMITED with other manufacturers, send every bidder the same dimensioned drawing, movement vector, pressure and temperature conditions, cycle requirement, materials, and acceptance criteria. That makes quotations comparable on engineering fit rather than an unsupported size label.

Related product

Duct Bellows

Duct Bellows

Duct Bellows

HVAC systems and industrial ducting rely on high-quality duct bellows for durability and performance.

View product →

Frequently asked questions

  • Which dimensions belong on an industrial duct bellows drawing?

    Show the duct opening, bellows face-to-face or relaxed length, end collars or cuffs, flange dimensions, bolt-hole details and the full installation envelope. State whether each dimension includes flanges, frames or clamps.

  • How do you measure the duct opening and installation gap on site?

    Measure the opening at several points after the duct is installed, record width and height separately, and measure the smallest available gap between mating faces. Record the measurement temperature and whether the duct is aligned, loaded or thermally expanded.

  • How should movement and the required relaxed length be calculated?

    Define axial compression, axial extension, lateral offset and angular movement at the operating condition. Use the supplier's movement limits to select the relaxed length, then check that the bellows does not bottom out, overextend or rub surrounding parts.

  • What flange and clearance details determine whether the bellows will fit?

    Specify flange outside dimensions, face width, thickness, bolt-hole diameter, pitch-circle or hole-spacing pattern, bolt access and gasket seating area. Check the installed bellows against nearby beams, insulation, duct supports and hot surfaces.

  • How should you document tolerances, inspection states and supplier acceptance?

    Place dimensional tolerances beside the affected dimensions, identify the relaxed and compressed inspection states, and require a drawing review covering opening size, length, movement, flange pattern, materials and acceptance measurements.